PowerFlex 40DiscontinuedVerified

Allen-Bradley PowerFlex 40 AC drive family · AC drive / VFD family · Rockwell Automation · Lifecycle: Discontinued

Last verified: 20 Sept 2026

PowerFlex 40 is a discontinued Allen-Bradley AC drive family. Rockwell's official migration path is PowerFlex 40 / 40P to PowerFlex 525. This is an engineering replacement family, not one universal catalog-number substitution.

What replaced it?

Current successor
PowerFlex 525 Verified

The current lifecycle endpoint. Not automatically a drop-in.

The historically correct solution and today's recommended endpoint can differ. See Methodology.

What is this part?

PowerFlex 525 is the current Rockwell family migration path for PowerFlex 40 and 40P installations. The exact 25B replacement depends on the old 22B catalog number and application.

Part numbers

Only the primary number is published so far.

Replacement / successor path

Current successor

PowerFlex 525Verified

The current lifecycle endpoint. Not automatically a drop-in.

Official Rockwell family migration path. Exact catalog number is application-specific and treated as an engineering replacement.

Is it plug-and-play?

Do not buy a generic PowerFlex 525 solely from horsepower. Check input voltage and phase, output current, enclosure, braking, digital and analog I/O, control wiring, communications, mounting dimensions and parameter conversion.

What must be checked before purchase?

Record the complete 22B catalog number and firmware, motor data, incoming supply, braking resistor, control wiring, network option, speed reference, relay/I/O use and panel dimensions. Use Rockwell's migration guidance to select the exact 25B catalog number.

Repair, exchange and bridge options

Individual discontinued PowerFlex 40 catalog pages may still show repairable/replaceable service options. Check the exact catalog number and region.

A repaired or tested legacy PowerFlex 40 can be a short-term bridge where appropriate, but the supported modernization direction is the PowerFlex 525 family.

Sources and evidence

Did this solve your problem?

Please do not include personal, confidential or sensitive information. Feedback may be retained for up to 12 months. Privacy Policy.

Compatibility information is evidence-based, but machine configuration can vary. Verify electrical, mechanical, software and safety requirements before purchase or installation.