SIMATIC S5 PLC family · PLC / automation platform family · Siemens · Lifecycle: Discontinued
Last verified: 20 Sept 2026
SIMATIC S5 is a discontinued Siemens PLC platform. For long-term modernization, Siemens provides S5-to-S7-1500 migration guidance. S7-1500 is a modernization platform, not a direct CPU swap: I/O, program behavior, HMI, drives, safety and process functions must be migrated deliberately.
What is this part?
An S5 modernization should preserve required machine/process behavior rather than mechanically translate hardware one-for-one. Current S7-1500 supports integrated motion-control functions, and current Siemens PID functions include PID_Compact and PID_Temp.
Part numbers
Only the primary number is published so far.
Replacement / successor path
Modernization successor
Part of a modernization path. Expect engineering work.
Official Siemens migration direction. Application-specific redesign/migration required.
| Relationship | Part | Confidence | Superseded since | What this means |
|---|---|---|---|---|
| Modernization successor | SIMATIC S7-1500 | Verified | — | Part of a modernization path. Expect engineering work. Official Siemens migration direction. Application-specific redesign/migration required. |
Is it plug-and-play?
Siemens explicitly notes that S5 and S7-1500 centralized I/O are not directly connectable. Depending on the existing system, migration can require wiring adapters, I/O redesign and application-specific CPU selection.
What must be checked before purchase?
Inventory the complete S5 rack and CPU/I/O catalog numbers. Back up STEP 5 source/EPROM data, HMI and recipes. Document digital/analog and temperature signals, PID tuning, fieldbus, drives/motors/encoders, safety circuits, timing and sequencing before selecting S7-1500 hardware.
Repair, exchange and bridge options
Remaining S5 spare availability decreases over time. Legacy spares can be an outage bridge but are not a long-term modernization strategy.
Sources and evidence
- Official migration guideVerifiedSIMATIC S5 to S7 migration guidecache.industry.siemens.com
States S5 has been discontinued since 2003 and documents hardware/application migration to S7-1500.
- OEMVerifiedSIMATIC S7-1500 PLCsiemens.com
Current platform with integrated motion-control capabilities.
- OEMVerifiedPID control function manualsupport.industry.siemens.com
Current PID documentation includes PID_Compact and PID_Temp.
Related research
Did this solve your problem?
Please do not include personal, confidential or sensitive information. Feedback may be retained for up to 12 months. Privacy Policy.
Compatibility information is evidence-based, but machine configuration can vary. Verify electrical, mechanical, software and safety requirements before purchase or installation.