HISTORICAL 10 · CASE #9
PASSPasmatic MSW 450/CW
Last verified: 20 Sept 2026
The blind run independently traced all three Rockwell migration families used in the real project.
Result
- Machine / component
- Pasmatic packaging machine / Rockwell legacy hardware
- Problem class
- Multi-family automation supersession
- Blind conclusion
- Locked before revealUse OEM migration paths per hardware family: PowerFlex 40/40P -> PowerFlex 525; Kinetix 6000 -> Kinetix 5700 as a coordinated servo-system migration; legacy MSR/Minotaur -> catalog/function-matched current safety solution. Preserve PLC/HMI behavior through controlled code changes and validation.
- Historical result
- The real modernization replaced nine MSR/Minotaur safety relays with GSR relays, three PowerFlex 40 drives with PowerFlex 525, and four Kinetix 6000 servo-system components with Kinetix 5700. PLC/HMI code was adapted and the work included safety documentation and validation.
- 2026 recommendation
- The same migration families remain appropriate, but every item must be mapped by exact catalog/function. Safety migration requires functional validation; Kinetix is a system migration, not a drop-in component swap.
- Verdict
- PASS
- Evidence quality
- A
How the case was solved
This was the strongest multi-family test: the blind result independently identified all three migration families and the need for code and safety revalidation before the historical project was revealed.
Evidence used
- Integrator caseHistorical solution sourcepciauto.com
- Official migration guidePowerFlex migrationrockwellautomation.com
- Official migration guideKinetix migration profileliterature.rockwellautomation.com
Did this solve your problem?
Please do not include personal, confidential or sensitive information. Feedback may be retained for up to 12 months. Privacy Policy.